Architectural & Industrial High-Bay Lighting Lux Level Verification Checklist
Illuminance mapping, Unified Glare Rating (UGR), DALI-2 automation, and emergency egress lighting compliance.
Stage 1: Photometric Illuminance Grid Mapping
Pass Inspection Item / Parameter Standard / Reference Recommended Acceptance / QA Criteria
Industrial Shop Floors & Machine Shops IS 3646 Recommended Benchmarks General manufacturing / foundry targeted 200–300 Lux; precision assembly targeted 500–750 Lux.
Warehousing & Logistics Aisles IS 3646 Recommended Benchmarks Racked aisles targeted 150–200 Lux; loading docks targeted 200 Lux; Uniformity ratio (Emin/Eavg) ≥ 0.60.
Commercial Offices & Workstations IS 3646 Recommended Benchmarks Desk working plane targeted 300–500 Lux; Color Rendering Index CRI ≥ 80.
Stage 2: Glare Control & Digital Control Protocols
Pass Inspection Item / Parameter Standard / Reference Recommended Acceptance / QA Criteria
Unified Glare Rating (UGR) CIE S 008 / IS 3646 UGR < 19 for workspaces and offices, evaluated based on room geometry, observer position, and luminaire layout.
DALI-2 & 0-10V Dimming Control IEC 62386 Individual and group luminaire addressing, daylight harvesting photocell sensitivity, and motion sensor delay verification.
Stage 3: Emergency Egress Lighting & Life Safety Compliance
Pass Inspection Item / Parameter Standard / Reference Recommended Acceptance / QA Criteria
Emergency Exit Illumination NBC 2016 Part 4 / Project Criterion Project emergency-lighting acceptance criterion: Minimum 10 Lux along designated escape corridors and exit doors, subject to applicable NBC/fire-authority requirements.
Central Battery Autonomy NBC 2016 / Local Fire Norms Continuous emergency battery illumination duration ≥ 90 minutes during complete AC mains failure.
Final Commissioning & Handover Sign-Off
Client Representative / Facility Head:

Name: ___________________________________

Company: ________________________________

Site Location: ___________________________

Signature & Date: _______________________
Certified Turnkey EPC Partner:

RS Electricals & HVAC Solutions

Senior Commissioning Engineer: ________________

Enlistment: Punjab Class-A Electrical Contractor

Helpline: +91 62399-13625 / +91 62399-13625
Classification of Technical Values: Numerical values identified as “Typical Engineering Design Targets” or “Recommended Acceptance / QA Criteria” are project-specific engineering benchmarks and company acceptance criteria. They are not necessarily universal statutory limits. Final requirements shall be determined from the applicable current edition of the governing standard, project specification, equipment manufacturer requirements and competent authority approvals.